Some losses have no single failed component to examine. Drives fail again after replacement, control boards last a fraction of their expected life, breakers trip with no fault to find. Furano Pacific Consulting investigates these losses by measurement, for insurers, adjusters, counsel and facility owners.
Signs that the cause is in the supply
- The same equipment fails repeatedly, or replacements fail the same way
- Failures cluster after outages, generator transfers or switching events
- Electronic equipment across unrelated systems fails early
- Breakers trip on ground fault or overload with no fault found
- Failures follow a change in load, such as new drives or LED lighting
What we measure
Harmonic distortion. Voltage and current harmonics and total demand distortion at the point of common coupling, assessed against IEEE 519.
Transients. Switching and lightning-induced overvoltages, captured as waveforms and compared with what the damaged components can withstand.
Sags, swells and interruptions. Recorded and classified to IEEE 1159, and matched against the times equipment tripped or failed.
Neutral, ground and leakage currents. Zero-sequence current, neutral loading and leakage through the grounding system, which protection can read as a fault.
Behaviour on standby power. A generator has a much higher source impedance than the utility supply, so the same load produces more voltage distortion. Some failures occur only then.
Logging is done with Class A analyzers to IEC 61000-4-30, for as long as the problem takes to show itself. An intermittent fault is not diagnosed in a site visit.
From measurement to cause
A measurement over a limit is not a cause. We connect what was measured to what failed: the failure mode of the damaged components, the timing of failures against recorded events, and the mechanism by which one produces the other. Suspects are tested the same way. A capacitor bank, a generator or a trip unit is confirmed or excluded on logged data, with the equipment switched in and out where that can be done.
Where the evidence does not support one cause, the report says so and states what each possible cause would need to be confirmed.
What the report gives you
- The cause or causes, with the measurements and the reasoning behind each
- The causes that were considered and excluded
- Whether the condition is in the facility, the utility supply or the equipment
- Mitigation that addresses the cause: filtering, detuned power factor correction, surge protection, changes to protection settings or to the standby supply
Recent investigations
Forensic power quality investigation — campus facility — Recurring drive failures traced to harmonic distortion beyond IEEE 519 limits, made far worse on standby power by the generator's source impedance.
Power quality and life-safety failure investigation — residential high-rise — Repeated fire alarm and access control failures investigated with metering and examination of the failed boards.
Power quality metering programme — agricultural producer — Recurring main breaker trips traced by long-term metering to leakage current from LED grow-light drivers.
Related
Forensic electrical engineering · Power quality · Equipment failure investigation · Insurance and legal
Send us a file
Submit an assignment with a description of the failures and any service records, or call 1 (866) 577-1894.