Skip to content

Case study

Power quality and life-safety failure investigation — residential high-rise

Repeated fire alarm and access control failures at a residential high-rise investigated with metering, service record analysis and examination of failed boards.

British Columbia · Forensic engineering · Power quality

A building owner retained us to establish why electronic equipment in a residential high-rise kept failing years ahead of its expected life.

Challenge

Over several years the building had a long run of service calls on its fire alarm and access control systems, and control boards across several systems were being replaced early. The owners suspected poor power quality, but the record also showed loose terminations, ground faults and water ingress. The task was to test the power quality theory with measurement and to state what the evidence did and did not support.

Approach

  • Site reviews of the electrical rooms, life-safety wiring and low-voltage systems
  • Analysis of the service records to sort failures by system and by reported cause
  • Power quality meters installed on the main distributions and logged over an extended period
  • Bench examination of failed circuit boards from the affected systems

Findings

Current distortion was well beyond the limit. Total demand distortion on both main distributions exceeded the IEEE 519 limit, at times by several multiples.

Voltage and loading were not the problem. Voltage distortion and supply voltage were within tolerance, and the distributions ran well below their ratings.

The failed boards told two stories. Some showed water staining and corrosion. One showed a component destroyed by overvoltage, consistent with a transient. Others gave no conclusive cause.

We did not force a single root cause. Where water damage was present, the evidence could not separate moisture from electrical stress, and the report says so.

Outcome

The owner received a remediation plan covering harmonic filtering, power factor correction, a check of transformer and neutral loading under the measured distortion, an audit of life-safety equipment for water damage, and continued logging.

Services applied

Forensic engineering and loss consulting · Power quality · Fire alarm system design

Commercial and architectural · All work

Talk to us about your project

More work

Talk to us about your project

Send us the scope and the constraints. We will tell you plainly whether we are the right firm for it — and if we are not, we will say so.