Western Canada · Risk engineering · Electrical engineering
A property owner retained us to assess a fleet of diesel standby generators that support life-safety systems, and to put a cost on repairing or replacing them.
Challenge
Most of the units were well past the service life expected of a standby generator set, parts were becoming hard to source, and the maintenance records were incomplete. The owner needed to know which units could be relied on, which needed work now, and what replacement would cost before committing capital.
Approach
- Nameplate survey and service history review for each unit
- On-site inspection and load testing with a generator service contractor
- Laboratory analysis of engine oil and coolant samples
- Review of the building, fire and electrical code changes that bear on a replacement
- Budget pricing from vendors and contractors, built up unit by unit
Findings
Most units were due for replacement. Age and parts availability, not a single defect, set the recommendation.
Load testing found what a visual inspection would not. One unit could not carry its rated load and needed immediate repair, with temporary generation during the work.
The fluid samples added to the picture. Several showed corrosion and contamination that pointed to specific maintenance actions.
Replacement may trigger code upgrades. Current codes are stricter on emergency feeders, generator rooms and fuel storage than those in force when the units were installed. The budget stated what it assumed could be reused.
Outcome
The owner received a repair list with contractor pricing for each unit, and a replacement budget covering generators, transfer switches, fuel systems, installation and commissioning, with contingency and exclusions stated.
Services applied
Risk engineering · Electrical engineering · Building systems design